FIRE SUPPRESSION SYSTEMS

Foam Based Fire Suppression Systems

Intensive and Effective Protection


Foam fire extinguishing systems are used to extinguish solid materials and flammable-inflammable liquid fires, which produce high energy in case of burning, at points where it is not possible to extinguish with water, by taking them under control.

Foam extinguishing system, which has a wide variety of application methods and system components, is a powerful extinguishing method used in a wide variety of situations such as aircraft hangars, transformers, warehouses, with foam concentrates that are resistant to alcohol or specially produced for hydrocarbon fires.

Certificates and Approvals of the Foam Extinguishing Systems We Offer

  • VdS
  • LPCB
  • UL Listed
  • CE
  • FM Approvals

System Types


System selection is determined by the type of fuel or combustible material that is planned to be extinguished. The most efficient system is selected by taking into account the test results of the foam concentrate to be used, the application area and the application time.

  • Low Expansion

    1:20 EXPANSION RATIO

    Applied with sprinkler heads.

  • Medium Expansion

    1:200 EXPANSION RATIO

    Applied with handheld devices.

  • High Expansion

    1:1000 EXPANSION RATIO

    Applied with an air mixture.

  • CAF System

    1:10 EXPANSION RATIO

    Combines air, water and foam.

System Components


In foam extinguishing systems, the extinguishing agent is made up of AFFF/AR-AFFF/SFFF type chemicals (SFFF: fluorine-free foam solution). Foam extinguishing systems can be designed for automatic or manual operation. The foam solution is generally used in extinguishing systems such as foam sprinkler systems, foam fire cabinets, tank suppression systems, foam monitor systems and foam generators. Foam extinguishing systems are widely used in areas containing flammable liquid chemicals, tank farms, petrochemical facilities, fuel transfer stations and aircraft hangars.

  • Storage Unit

    Atmospheric or membrane bladder tanks in the range of 100-20000lt.

  • Alarm and Control Valves

    Deluge alarm and foam valve set for extinguishing area control.

  • Foam Concentrate

    AFFF or AR-AFFF dense chemical foam miscible with water at 1%, 3% and 6%.

  • Proportioners

    Equipment that mixes the foam drawn from the tank and the water passing through the valve at the desired rate.

  • Nozzles

    Open-ended nozzle, foaming units, foam cells, monitor and fan foam generators.

  • Detection System

    Double verification detector, panel, button and alarm equipment triggering the mechanism.

Foam Based Systems


The foam, which acts as an extinguishing fluid, is mixed with water and delivered to the discharge heads with pressurized water provided by the fire pump. The piping is kept empty. Black steel pipes are preferred because galvanized piping will react with the foam. The foam discharged from the nozzles covers the flammable liquids and forms a blanket layer. Thanks to this layer, the contact of the fuel, which has heat energy, with oxygen is cut off and the reaction of the fire triangle is stopped. Another important point in foam extinguishing systems is that all components used, such as foam concentrate, tank, proportioner, nozzle and valve, must have a common approval.

Foam suppression system pump and proportioner unit

Installation

Application areas of foam fire extinguishing systems;
  • Above Ground Tanks
  • Hangars, Airfield
  • Flammable Liquid & Tire Storage
  • Generator, Transformers

Advantages

Compared with water or gas suppression;
  • Protection in High Warehouses
  • Can be used on all fire loads
  • Can be used in open areas
  • Large foam storage volume

System Applications


Foam extinguishing systems are designed in similar standards with aqueous systems and NFPA11, 16, 30, 409 standards are used. Protein-based, synthetic-based, aqua film-forming, alcohol-resistant foam types and foam concentrate suitable for combustible materials are selected. Double-stage verification fire detection systems used in gas extinguishing systems are used for the activation of foam extinguishing systems. While flame detectors are used for flammable liquids, smoke detectors can be preferred in closed areas for materials that produce dense smoke. In the hydraulic calculations of foam extinguishing systems, details such as piping and shot head diameters are determined by using the omniCAD software used in water extinguishing systems.

  • Fuel tank installed outdoors with foam tank protection system
    Tank dike and in-tank protection
  • Ground-mounted grate foam nozzle
    Grate NozzleGround protection application
  • Medium-expansion foam intervention using a handheld foam branch
    Medium expansion manual intervention